Confirm CT Physical Installation (Most Common Cause)
-
CT check correct
Before this test, be sure you commissioned the CT check correctly in FranklinWH App.
-
CT Location
Must be installed at PCC: Utility Meter → CT → Main Breaker
If any house load, subpanel, or PV is wired before the CTs, aGate can’t measure it → permanent mismatch.
-
Identify Unmeasured Loads
Any circuit fed before the PCC CTs is invisible to aGate.
Examples: AC, pool pump, subpanel on utility side of CT → only utility meter reads it, aGate does not.
This is a permanent mismatch unless wiring is reworked.
4. Real-Time Live Comparison Test
-
Turn off large cycling loads (AC, water heater).
-
Run a fixed known load (e.g., 1500W space heater only).
-
Compare:
-
Utility meter real-time kW
-
aGate grid kW
-
If values differ greatly → CT installation/config error.
-
If values match closely → mismatch is from unmeasured loads or time drift.